§ 18.24. Electrical clearances.
78 words·~1 min read·
/us/cfr/t30/s§ 18.24·A research copy — for the controlling text, always check the official state or federal source. Not legal advice.
Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows: ::: {width="100%"} ::: {.table_head} Minimum Clearances Between Uninsulated Surfaces ::: ::: {.gpotbl_div} Phase-to-Phase Voltage